Inspection-Report_TFSAFE_Full_KFAB22_Oiltown-Combat-COMMS_116_05-06-26_1-7
CompleteReport Details
- TAG-ID
- TFSAFE_KFAB22_Oiltown-Combat-COMMS_116_05-06-26_1-7
- Work Order
- TFS-KFAB22-2026-00005
- Site
- KFAB (Jordan) (KFAB22)
- Building
- Oiltown-Combat-COMMS
- Building Type
- OFFICE
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 05-JUN-2026
- Team
- 116
- Overall Rating
- Fair
- Location
- Oiltown is adjacent to the airfield, north of Dufftown. The Combat COMMS office is within Oiltown.
Summary of Findings
1x CDP. 3x 4’ light fittings. 4x double sockets. 2x 2-gang light switches. 2x internal AC isolators. 2x external AC isolators. 2x external light fittings.
Building Picture
Deficiencies (7)
Location: At CDP.
Category: Improper Use / Damaged
Equipment: CDP
Occurrences: 10
Imminent Danger: No
Code Source: British Standard
Code Reference: 132: Protection against electric shock
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Breaker blanks missing from dead front.
Location: Within the CDP.
Category: Improper Use / Damaged
Equipment: CDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 132: Protection against electric shock
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Type AC RCD used. Type AC RCD is not suitable for this building.
Location: All circuits.
Category: Grounding and Bonding
Equipment: CDP
Occurrences: 6
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To: O&M Provider
Description: High Zs reading of 1462 ohms throughout the office.
Location: Within internal light fixtures.
Category: Improper Terminations
Equipment: WLT
Occurrences: 9
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Twist taped connections on live, neutral, and CPC.
Location: At light switches.
Category: Grounding and Bonding
Equipment: WLT
Occurrences: 2
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To: O&M Provider
Description: No CPC at light switches.
Location: At external AC condensers.
Category: Unlisted Equipment
Equipment: WLT
Occurrences: 2
Imminent Danger: No
Code Source: British Standard
Code Reference: 511: Compliance with standards
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Unlisted cables.
Location: At external AC condensers.
Category: Improper Use / Damaged
Equipment: WLT
Occurrences: 2
Imminent Danger: No
Code Source: British Standard
Code Reference: 522: Selection and erection of wiring systems in relation to external influences
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Cable clips not used: strain on terminations.
Signatures & QC
Inspector 1: Salomon Munoz
Inspector 2: Jongi Ledbetter
QC: David Forbes (approved 05-JUN-2026)
Status History
2
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 05-JUN-2026 | Pending QC | QC Approved | David Forbes | |
| 05-JUN-2026 | Draft | Pending QC | Salomon Munoz |