Report Details

TAG-ID
TFSAFE_KFAB22_Oiltown-NIPR_116_06-06-26_1-6
Work Order
TFS-KFAB22-2026-00006
Site
KFAB (Jordan) (KFAB22)
Building
Oiltown-NIPR
Building Type
OFFICE
System Voltage
230/400
Code Standard
British Standard

Inspection Info

Phase
Full Inspection
Date
06-JUN-2026
Team
116
Overall Rating
Fair
Location
Oiltown is adjacent to the airfield, north of Dufftown. The NIPR office is within Oiltown.

Summary of Findings

Items inspected: 1x CDP. 3x 4’ light fittings. 4x double sockets. 2x 2-gang light switches. 2x internal AC isolators. 2x external AC isolators. 2x external light fittings. 2x external lights.

Building Picture

Building photo

Deficiencies (6)

Deficiency #1 RAC 2 Open

Location: At CDP.

Category: Improper Use / Damaged

Equipment: CDP

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 132: Protection against electric shock

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Breaker blank missing from dead front.

Deficiency photo
Deficiency #2 RAC 2 Open

Location: Within the CDP.

Category: Improper Use / Damaged

Equipment: CDP

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 132: Protection against electric shock

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Type AC RCD used. Type AC RCD is not suitable for this building.

Deficiency photo
Deficiency #3 RAC 2 Open

Location: All circuits.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 6

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: High Zs reading of 1481 ohms throughout the office.

Deficiency photo
Deficiency #4 RAC 2 Open

Location: Within lighting circuit including switches.

Category: Grounding and Bonding

Equipment: LTG

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: No CPC to lighting circuit.

Deficiency photo
Deficiency #5 RAC 2 Open

Location: At external AC condensers.

Category: Improper Use / Damaged

Equipment: WLT

Occurrences: 2

Imminent Danger: No

Code Source: British Standard

Code Reference: 522: Selection and erection of wiring systems in relation to external influences

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Cable clips not used: strain on terminations.

Deficiency photo
Deficiency #6 RAC 2 Open

Location: Within external AC condensers supply cables.

Category: Unlisted Equipment

Equipment: WLT

Occurrences: 2

Imminent Danger: No

Code Source: British Standard

Code Reference: 511: Compliance with standards

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Unlisted cables.

Deficiency photo

Signatures & QC

Inspector 1: Salomon Munoz

Inspector 2: Jongi Ledbetter

QC: David Forbes (approved 08-JUN-2026)

Status History

2
DateFromToChanged ByNotes
08-JUN-2026Pending QCQC ApprovedDavid Forbes
06-JUN-2026DraftPending QCSalomon Munoz
📄 Download PDFCreate Re-inspection 1Back to Work OrderAll Reports