Report Details

TAG-ID
TFSAFE_KFAB22_Oiltown-EC-130-MX_116_09-06-26_1-6
Work Order
TFS-KFAB22-2026-00010
Site
KFAB (Jordan) (KFAB22)
Building
Oiltown-EC-130-MX
Building Type
OFFICE
System Voltage
230/400
Code Standard
British Standard

Inspection Info

Phase
Full Inspection
Date
09-JUN-2026
Team
116
Overall Rating
Fair
Location
Oiltown is adjacent to the airfield, north of Dufftown. The EC-130 MX office is within Oiltown.

Summary of Findings

Items inspected: 1x CDP. 3x 4’ light fittings. 4x double sockets. 2x 2-gang light switches. 2x internal AC isolators. 2x external AC isolators. 2x external light fittings.

Building Picture

Building photo

Deficiencies (6)

Deficiency #1 RAC 2 Open

Location: Within the CDP.

Category: Improper Use / Damaged

Equipment: CDP

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 132: Protection against electric shock

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Type AC RCD used. Type AC RCD is not suitable for this building.

Deficiency photo
Deficiency #2 RAC 2 Open

Location: At wall switches near entrances.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 2

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: No CPC to switches.

Deficiency photo
Deficiency #3 RAC 2 Open

Location: All circuits.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 6

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: High Zs reading of 896 ohms throughout office.

Deficiency photo
Deficiency #4 RAC 2 Open

Location: At external AC condensers.

Category: Improper Use / Damaged

Equipment: WLT

Occurrences: 2

Imminent Danger: No

Code Source: British Standard

Code Reference: 522: Selection and erection of wiring systems in relation to external influences

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Cable clips not used: strain on terminations.

Deficiency photo
Deficiency #5 RAC 2 Open

Location: At external AC condensers.

Category: Unlisted Equipment

Equipment: WLT

Occurrences: 2

Imminent Danger: No

Code Source: British Standard

Code Reference: 511: Compliance with standards

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Unlisted cables.

Deficiency photo
Deficiency #6 RAC 2 Closed / Repaired

Location: At external AC condensers.

Category: Improper Terminations

Equipment: WLT

Occurrences: 2

Imminent Danger: No

Code Source: British Standard

Code Reference: 642: Inspection

Action Taken: N/A

SOR Issued To: Task Force SAFE

Description: Loose terminations on the neutral. (Buzzing noise heard on both AC condensers) Repaired on the spot by TF SAFE.

Deficiency photo

Signatures & QC

Inspector 1: Salomon Munoz

Inspector 2: Jongi Ledbetter

QC: David Forbes (approved 10-JUN-2026)

Status History

4
DateFromToChanged ByNotes
10-JUN-2026Pending QCQC ApprovedDavid Forbes
10-JUN-2026QC RejectedPending QCSalomon Munoz
09-JUN-2026Pending QCQC RejectedDavid ForbesDef 6; Deficiency is Open but has been repaired on the spot by TF SAFE
09-JUN-2026DraftPending QCSalomon Munoz