Inspection-Report_TFSAFE_Full_KATAB_29100-Warehouse-EXT-_128_13-06-26_1-4
QC RejectedReport Details
- TAG-ID
- TFSAFE_KATAB_29100-Warehouse-EXT-_128_13-06-26
- Work Order
- TFS-KATAB-2026-00001
- Site
- KA2AB (Jordan) (KATAB)
- Building
- 29100-Warehouse-EXT
- Building Type
- OTHER
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 13-JUN-2026
- Team
- 128
- Overall Rating
- Fair
- Location
- Camp Xiphos warehouse is located within the expansion area next to the fuel pad within Camp Xiphos.
Building Picture
Update Report
Deficiencies (4)
Location: Enclosure for isolator supplying air handling unit, south western corner.
Category: Grounding and Bonding
Equipment: WLT
Occurrences: 2
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Enclosure has not been bonded.
Location: Within enclosure for isolator supplying air handling unit, south western corner.
Category: Grounding and Bonding
Equipment: WLT
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To:
Description: No bonding from earth tags to enclosure as glanding plate is insulated, preventing earth path
Location: Enclosure for isolator supplying air handling unit, south western corner.
Category: Grounding and Bonding
Equipment: WLT
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Door has not been bonded.
Location: External lighting, above all three entrances.
Category: Unlisted Equipment
Equipment: WLT
Occurrences: 3
Imminent Danger: No
Code Source: British Standard
Code Reference: 511: Compliance with standards
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Light fixtures are unlisted. Data sheet required.
Signatures & QC
Comments: Report Details; Building name 29100-Warehouse-EXT- needs the – removed from the end of the name Deficiency 2; Location and description have been mixed up and needs changed
Please address the issues above and resubmit.
Status History
2
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 15-JUN-2026 | Pending QC | QC Rejected | David Forbes | Report Details; Building name 29100-Warehouse-EXT- needs the – removed from the end of the name Deficiency 2; Location and description have been mixed up and needs changed |
| 13-JUN-2026 | Draft | Pending QC | Andrew McLean |