⚠ QC Rejected by David Forbes
View Full History
Latest Comments: Report Details;
Building name 29100-Warehouse-EXT- needs the – removed from the end of the name
Deficiency 2;
Location and description have been mixed up and needs changed

Report Details

TAG-ID
TFSAFE_KATAB_29100-Warehouse-EXT-_128_13-06-26
Work Order
TFS-KATAB-2026-00001
Site
KA2AB (Jordan) (KATAB)
Building
29100-Warehouse-EXT
Building Type
OTHER
System Voltage
230/400
Code Standard
British Standard

Inspection Info

Phase
Full Inspection
Date
13-JUN-2026
Team
128
Overall Rating
Fair
Location
Camp Xiphos warehouse is located within the expansion area next to the fuel pad within Camp Xiphos.

Building Picture

Building photo

Update Report

Deficiencies (4)

Deficiency #1 RAC 2 Closed / Repaired
Edit

Location: Enclosure for isolator supplying air handling unit, south western corner.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 2

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Enclosure has not been bonded.

Deficiency photo
Deficiency #2 RAC 2 Closed / Repaired
Edit

Location: Within enclosure for isolator supplying air handling unit, south western corner.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To:

Description: No bonding from earth tags to enclosure as glanding plate is insulated, preventing earth path

Deficiency photo
Deficiency #3 RAC 2 Closed / Repaired
Edit

Location: Enclosure for isolator supplying air handling unit, south western corner.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Door has not been bonded.

Deficiency photo
Deficiency #4 RAC 2 Closed / Repaired
Edit

Location: External lighting, above all three entrances.

Category: Unlisted Equipment

Equipment: WLT

Occurrences: 3

Imminent Danger: No

Code Source: British Standard

Code Reference: 511: Compliance with standards

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Light fixtures are unlisted. Data sheet required.

Deficiency photo

Signatures & QC

QC Rejected by: David Forbes (Rejection #1)

Comments: Report Details; Building name 29100-Warehouse-EXT- needs the – removed from the end of the name Deficiency 2; Location and description have been mixed up and needs changed

Please address the issues above and resubmit.


Status History

2
DateFromToChanged ByNotes
15-JUN-2026Pending QCQC RejectedDavid ForbesReport Details; Building name 29100-Warehouse-EXT- needs the – removed from the end of the name Deficiency 2; Location and description have been mixed up and needs changed
13-JUN-2026DraftPending QCAndrew McLean
Back to Work OrderAll Reports