Report Details

TAG-ID
TFSAFE_KFAB22_Oiltown-AMOPS_116_15-06-26_1-6
Work Order
TFS-KFAB22-2026-00015
Site
KFAB (Jordan) (KFAB22)
Building
Oiltown-AMOPS
Building Type
OFFICE
System Voltage
230/400
Code Standard
British Standard

Inspection Info

Phase
Full Inspection
Date
15-JUN-2026
Team
116
Overall Rating
Fair
Location
Oiltown is adjacent to the airfield, north of Dufftown. The AMOPS office is within Oiltown.

Summary of Findings

Items inspected: 1x CDP. 3x Internal lights. 3x External lights 3x Double sockets. 3x Single sockets. 3x 2-gang switches. 6x AC isolators for 3x AC systems.

Building Picture

Building photo

Deficiencies (6)

Deficiency #1 RAC 2 Open

Location: At CDP.

Category: Improper Use / Damaged

Equipment: CDP

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 132: Protection against electric shock

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Breaker blank missing from dead front.

Deficiency photo
Deficiency #2 RAC 2 Open

Location: Within the CDP.

Category: Improper Use / Damaged

Equipment: CDP

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 132: Protection against electric shock

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Type AC RCD used. Type AC RCD is not suitable for this building.

Deficiency photo
Deficiency #3 RAC 2 Open

Location: At light switches.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 3

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: No CPC at light switches.

Deficiency photo
Deficiency #4 RAC 2 Open

Location: All circuits.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 6

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: High Zs reading of 1207 ohms throughout the office.

Deficiency photo
Deficiency #5 RAC 2 Open

Location: At external AC condensers.

Category: Unlisted Equipment

Equipment: WLT

Occurrences: 3

Imminent Danger: No

Code Source: British Standard

Code Reference: 511: Compliance with standards

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Unlisted cables.

Deficiency photo
Deficiency #6 RAC 2 Open

Location: At external AC condensers.

Category: Improper Use / Damaged

Equipment: WLT

Occurrences: 3

Imminent Danger: No

Code Source: British Standard

Code Reference: 522: Selection and erection of wiring systems in relation to external influences

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Cable clips not used: strain on terminations.

Deficiency photo

Signatures & QC

Inspector 1: Salomon Munoz

Inspector 2: Jongi Ledbetter

QC: David Forbes (approved 15-JUN-2026)

Status History

2
DateFromToChanged ByNotes
15-JUN-2026Pending QCQC ApprovedDavid Forbes
15-JUN-2026DraftPending QCSalomon Munoz
📄 Download PDFCreate Re-inspection 1Back to Work OrderAll Reports