Inspection-Report_TFSAFE_Full_KATAB_29100-Warehouse-EXT_128_16-06-26_1-4
CompleteReport Details
- TAG-ID
- TFSAFE_KATAB_29100-Warehouse-EXT_128_16-06-26_1-4
- Work Order
- TFS-KATAB-2026-00004
- Site
- KA2AB (Jordan) (KATAB)
- Building
- 29100-Warehouse-EXT
- Building Type
- OTHER
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 16-JUN-2026
- Team
- 128
- Overall Rating
- Fair
- Location
- Camp Xiphos warehouse is located within the expansion area next to the fuel pad within Camp Xiphos.
Building Picture
Deficiencies (4)
Location: Within enclosure for isolator supplying air handling unit, south western corner.
Category: Grounding and Bonding
Equipment: WLT
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Enclosure has not been bonded.
Location: Within enclosure for isolator supplying air handling unit, south western corner.
Category: Grounding and Bonding
Equipment: WLT
Occurrences: 3
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To: O&M Provider
Description: No bonding from earth tags to enclosure as glanding plate is insulated, preventing earth path.
Location: Enclosure door.
Category: Grounding and Bonding
Equipment: WLT
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Door has not been bonded.
Location: External lighting, above all three entrances.
Category: Unlisted Equipment
Equipment: WLT
Occurrences: 3
Imminent Danger: No
Code Source: British Standard
Code Reference: 511: Compliance with standards
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Light fixtures are unlisted. Data sheet required.
Signatures & QC
Inspector 1: Andrew McLean
Inspector 2: Brett Smithson
QC: David Forbes (approved 17-JUN-2026)
Status History
6
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 17-JUN-2026 | Pending QC | QC Approved | David Forbes | |
| 17-JUN-2026 | QC Rejected | Pending QC | Andrew McLean | |
| 17-JUN-2026 | Pending QC | QC Rejected | David Forbes | Deficiency 2; Description; missing- path. |
| 17-JUN-2026 | QC Rejected | Pending QC | Andrew McLean | |
| 16-JUN-2026 | Pending QC | QC Rejected | David Forbes | Deficiency 1 Closed previously needs changed to closed / repaired |
| 16-JUN-2026 | Draft | Pending QC | Andrew McLean |