Report Details

TAG-ID
TFSAFE_KATAB_29100-Warehouse-EXT_128_16-06-26_1-4
Work Order
TFS-KATAB-2026-00004
Site
KA2AB (Jordan) (KATAB)
Building
29100-Warehouse-EXT
Building Type
OTHER
System Voltage
230/400
Code Standard
British Standard

Inspection Info

Phase
Full Inspection
Date
16-JUN-2026
Team
128
Overall Rating
Fair
Location
Camp Xiphos warehouse is located within the expansion area next to the fuel pad within Camp Xiphos.

Building Picture

Building photo

Deficiencies (4)

Deficiency #1 RAC 2 Closed / Repaired

Location: Within enclosure for isolator supplying air handling unit, south western corner.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Enclosure has not been bonded.

Deficiency photo
Deficiency #2 RAC 2 Closed / Repaired

Location: Within enclosure for isolator supplying air handling unit, south western corner.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 3

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: No bonding from earth tags to enclosure as glanding plate is insulated, preventing earth path.

Deficiency photo
Deficiency #3 RAC 2 Closed / Repaired

Location: Enclosure door.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Door has not been bonded.

Deficiency photo
Deficiency #4 RAC 2 Closed / Repaired

Location: External lighting, above all three entrances.

Category: Unlisted Equipment

Equipment: WLT

Occurrences: 3

Imminent Danger: No

Code Source: British Standard

Code Reference: 511: Compliance with standards

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Light fixtures are unlisted. Data sheet required.

Deficiency photo

Signatures & QC

Inspector 1: Andrew McLean

Inspector 2: Brett Smithson

QC: David Forbes (approved 17-JUN-2026)

Status History

6
DateFromToChanged ByNotes
17-JUN-2026Pending QCQC ApprovedDavid Forbes
17-JUN-2026QC RejectedPending QCAndrew McLean
17-JUN-2026Pending QCQC RejectedDavid ForbesDeficiency 2; Description; missing- path.
17-JUN-2026QC RejectedPending QCAndrew McLean
16-JUN-2026Pending QCQC RejectedDavid ForbesDeficiency 1 Closed previously needs changed to closed / repaired
16-JUN-2026DraftPending QCAndrew McLean
📄 Download PDFCreate Re-inspection 1Back to Work OrderAll Reports