Report Details

TAG-ID
TFSAFE_7NX32_Hangar-RM-1_128_16-06-26_1-3
Work Order
TFS-7NX32-2026-00001
Site
H-5 (Jordan) (7NX32)
Building
Hangar-RM-1
Building Type
HANGAR
System Voltage
230/400
Code Standard
British Standard

Inspection Info

Phase
Full Inspection
Date
16-JUN-2026
Team
128
Overall Rating
Fair
Location
Hangar is located adjacent to the flightline. Rm-1 FSR office is located on right side of building as entered from the car park, West wall.

Building Picture

Building photo

Deficiencies (3)

Deficiency #1 RAC 2 Closed / Repaired

Location: AC units

Category: Improper Terminations

Equipment: WLT

Occurrences: 5

Imminent Danger: No

Code Source: British Standard

Code Reference: 526: Electrical connections

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Poor terminations on AC grounds.

Deficiency photo
Deficiency #2 RAC 2 Closed / Repaired

Location: Light switch is located in the right hand office inside Rm-1.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: No CPC at light switch.

Deficiency photo
Deficiency #3 RAC 2 Open

Location: LED drivers at light fixtures.

Category: Unlisted Equipment

Equipment: WLT

Occurrences: 24

Imminent Danger: No

Code Source: British Standard

Code Reference: 511: Compliance with standards

Action Taken: N/A

SOR Issued To: O&M Provider

Description: LED drivers are unlisted. Data sheet required.

Deficiency photo

Signatures & QC

Inspector 1: Andrew McLean

Inspector 2: Brett Smithson

QC: David Forbes (approved 17-JUN-2026)

Status History

4
DateFromToChanged ByNotes
17-JUN-2026Pending QCQC ApprovedDavid Forbes
17-JUN-2026QC RejectedPending QCAndrew McLean
17-JUN-2026Pending QCQC RejectedDavid ForbesCorrections needed on number of deficiencies that we talked about