Inspection-Report_TFSAFE_Full_7NX32_Hangar-RM-1_128_16-06-26_1-3
CompleteReport Details
- TAG-ID
- TFSAFE_7NX32_Hangar-RM-1_128_16-06-26_1-3
- Work Order
- TFS-7NX32-2026-00001
- Site
- H-5 (Jordan) (7NX32)
- Building
- Hangar-RM-1
- Building Type
- HANGAR
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 16-JUN-2026
- Team
- 128
- Overall Rating
- Fair
- Location
- Hangar is located adjacent to the flightline. Rm-1 FSR office is located on right side of building as entered from the car park, West wall.
Building Picture
Deficiencies (3)
Location: AC units
Category: Improper Terminations
Equipment: WLT
Occurrences: 5
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Poor terminations on AC grounds.
Location: Light switch is located in the right hand office inside Rm-1.
Category: Grounding and Bonding
Equipment: WLT
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To: O&M Provider
Description: No CPC at light switch.
Location: LED drivers at light fixtures.
Category: Unlisted Equipment
Equipment: WLT
Occurrences: 24
Imminent Danger: No
Code Source: British Standard
Code Reference: 511: Compliance with standards
Action Taken: N/A
SOR Issued To: O&M Provider
Description: LED drivers are unlisted. Data sheet required.
Signatures & QC
Inspector 1: Andrew McLean
Inspector 2: Brett Smithson
QC: David Forbes (approved 17-JUN-2026)
Status History
4
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 17-JUN-2026 | Pending QC | QC Approved | David Forbes | |
| 17-JUN-2026 | QC Rejected | Pending QC | Andrew McLean | |
| 17-JUN-2026 | Pending QC | QC Rejected | David Forbes | Corrections needed on number of deficiencies that we talked about |
| 16-JUN-2026 | Draft | Pending QC | Andrew McLean |