Inspection-Report_TFSAFE_Full_7NX32_Hangar-RM-2_128_17-06-26_1-3
CompleteReport Details
- TAG-ID
- TFSAFE_7NX32_Hangar-RM-2_128_17-06-26_1-3
- Work Order
- TFS-7NX32-2026-00004
- Site
- H-5 (Jordan) (7NX32)
- Building
- Hangar-RM-2
- Building Type
- HANGAR
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 17-JUN-2026
- Team
- 128
- Overall Rating
- Fair
- Location
- Hangar is located adjacent to the flightline. Rm-2 is located on right side of building as entered from the car park, West wall.
Building Picture
Deficiencies (3)
Location: AC units, back wall.
Category: Improper Terminations
Equipment: WLT
Occurrences: 2
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: CPC is poorly terminated.
Location: LED drivers at light fixtures.
Category: Unlisted Equipment
Equipment: WLT
Occurrences: 9
Imminent Danger: No
Code Source: British Standard
Code Reference: 511: Compliance with standards
Action Taken: N/A
SOR Issued To: O&M Provider
Description: LED drivers are unlisted. Data sheet required.
Location: Cables above the ceiling at the light fixtures.
Category: Improper Use / Damaged
Equipment: WLT
Occurrences: 9
Imminent Danger: No
Code Source: British Standard
Code Reference: 522: Selection and erection of wiring systems in relation to external influences
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Exposed single insulated cables above the ceiling.
Signatures & QC
Inspector 1: Brett Smithson
Inspector 2: Andrew McLean
QC: David Forbes (approved 19-JUN-2026)
Status History
4
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 19-JUN-2026 | Pending QC | QC Approved | David Forbes | |
| 17-JUN-2026 | QC Rejected | Pending QC | Brett Smithson | |
| 17-JUN-2026 | Pending QC | QC Rejected | David Forbes | Need to add other deficiencies as we talked about |
| 17-JUN-2026 | Draft | Pending QC | Brett Smithson |