Inspection-Report_TFSAFE_Full_ALQ26_GEN-3-W_113_17-06-26_0
CompleteReport Details
- TAG-ID
- TFSAFE_ALQ26_GEN-3-W_113_17-06-26_0
- Work Order
- TFS-ALQ26-2026-00014
- Site
- Al Quwayrah (ALQ26)
- Building
- GEN-3-W
- Building Type
- GENERATOR
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 17-JUN-2026
- Team
- 113
- Overall Rating
- Fair
- Location
- Located on the western perimeter.
Summary of Findings
GEN-3 of 3. Generator serial number - LWL11011. Generator is on standby, not running at this time. All cabling, terminations and earthing arrangements. Neutral/earth link is located at the MDP. No LHS deficiencies found. GEN-3 ground electrode conductor is 300mm2 and is run from the MET within GEN-3 and via the MET within the ATS, then terminating to two ground rods spaced 9ft apart.
Building Picture
Deficiencies (0)
No deficiencies recorded yet.
Signatures & QC
Inspector 1: Jon Sharp
Inspector 2: Giles Vincent-Edwards
QC: David Forbes (approved 17-JUN-2026)
Status History
2
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 17-JUN-2026 | Pending QC | QC Approved | - | |
| 17-JUN-2026 | Draft | Pending QC | Jonathan Sharp |