Report Details

TAG-ID
TFSAFE_ALQ26_GEN-3-W_113_17-06-26_0
Work Order
TFS-ALQ26-2026-00014
Site
Al Quwayrah (ALQ26)
Building
GEN-3-W
Building Type
GENERATOR
System Voltage
230/400
Code Standard
British Standard

Inspection Info

Phase
Full Inspection
Date
17-JUN-2026
Team
113
Overall Rating
Fair
Location
Located on the western perimeter.

Summary of Findings

GEN-3 of 3. Generator serial number - LWL11011. Generator is on standby, not running at this time. All cabling, terminations and earthing arrangements. Neutral/earth link is located at the MDP. No LHS deficiencies found. GEN-3 ground electrode conductor is 300mm2 and is run from the MET within GEN-3 and via the MET within the ATS, then terminating to two ground rods spaced 9ft apart.

Building Picture

Building photo

Deficiencies (0)

No deficiencies recorded yet.

Signatures & QC

Inspector 1: Jon Sharp

Inspector 2: Giles Vincent-Edwards

QC: David Forbes (approved 17-JUN-2026)

Status History

2
DateFromToChanged ByNotes
17-JUN-2026Pending QCQC Approved-
17-JUN-2026DraftPending QCJonathan Sharp
📄 Download PDFCreate Re-inspection 1Back to Work OrderAll Reports