Inspection-Report_TFSAFE_Full_ALQ26_SDP-2-W_113_18-06-26_1-8
CompleteReport Details
- TAG-ID
- TFSAFE_ALQ26_SDP-2-W_113_18-06-26_1-8
- Work Order
- TFS-ALQ26-2026-00015
- Site
- Al Quwayrah (ALQ26)
- Building
- SDP-2-W
- Building Type
- SDP
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 18-JUN-2026
- Team
- 113
- Overall Rating
- Fair
- Location
- Located on the western perimeter, north of laundry.
Summary of Findings
x 1 SDP. x 1 100A 3P MCCB. x 6 63A 1P MCCB's. x 6 40A 1P MCCB's. x 11 32A 3P MCCB's. All cabling, terminations and earthing arrangements. Ze readings are within the maximum permitted tolerance of 0.8 Ohms.
Building Picture
Deficiencies (8)
Location: SDP-2-W
Category: Improper Use / Damaged
Equipment: SDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 642: Inspection
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Locking mechanism to door is damaged and secured with wire and self-tapping screws. Access requires the use of a tool. SDP-2-W is fenced off and access restricted.
Location: Within SDP.
Category: Grounding and Bonding
Equipment: GND
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To: O&M Provider
Description: No supplementary bond present to door.
Location: Within SDP.
Category: Improper Use / Damaged
Equipment: SDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 132: Protection against electric shock
Action Taken: N/A
SOR Issued To: O&M Provider
Description: No dead front present within SDP. Access requires the use of a tool. SDP-2-W is fenced off and access restricted.
Location: Within SDP enclosure, circuit 15/L2 and 15/L3.
Category: Poor Workmanship
Equipment: SDP
Occurrences: 2
Imminent Danger: Yes
Code Source: British Standard
Code Reference: 132: Protection against electric shock
Action Taken: TF Safe isolated circuits and made safe on the spot.
SOR Issued To: Task Force SAFE
Description: Exposed live ends to redundant outgoing circuits.
Location: Within SDP, circuit 7/TP.
Category: Grounding and Bonding
Equipment: GND
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To: O&M Provider
Description: SWA gland to circuit 7/TP has been incorrectly fitted. Earth path is relying solely on the steel wire armouring.
Location: Within SDP.
Category: Improper Use / Damaged
Equipment: SDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 510: Common rules
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Gland to outgoing circuit is damaged, removing abrasion protection to single insulated 3-phase conductors.
Location: Within SDP, circuit 15/L1.
Category: Improper Use / Damaged
Equipment: SDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: Appx 4: Current carrying capacities and voltage drop for cables
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Circuit 15/L1 - 6mm2 conductors fed from 63A MCCB.
Location: Within SDP, circuit 8/TP, 11/TP, 14/TP, 17/TP and 18/TP.
Category: Poor Workmanship
Equipment: SDP
Occurrences: 15
Imminent Danger: No
Code Source: British Standard
Code Reference: 510: Common rules
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Redundant outgoing circuits have bare ends left exposed.
Signatures & QC
Inspector 1: Jon Sharp
Inspector 2: Giles Vincent-Edwards
QC: David Forbes (approved 22-JUN-2026)
Status History
4
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 22-JUN-2026 | Pending QC | QC Approved | David Forbes | |
| 20-JUN-2026 | QC Rejected | Pending QC | Jonathan Sharp | |
| 19-JUN-2026 | Pending QC | QC Rejected | David Forbes | Deficiency 8; SOR Issued To: O&M Provider should this be Task Force SAFE? |
| 18-JUN-2026 | Draft | Pending QC | - |