Report Details

TAG-ID
TFSAFE_ALQ26_ATS-N_113_03-06-26_1
Work Order
TFS-ALQ26-2026-00002
Site
Al Quwayrah (ALQ26)
Building
ATS-N
Building Type
ATS
System Voltage
230/400
Code Standard
British Standard

Inspection Info

Phase
Full Inspection
Date
03-JUN-2026
Team
113
Overall Rating
Fair
Location
North perimeter rear of DFAC.

Summary of Findings

All cabling, terminations and earthing arrangements inspected. Note: 3-phase 4-wire parallel supply within ATS from GEN-1. The Neutral/earth link installed within GEN-1 is for the GEC at MET. GEN-2 is a 3-phase 4-wire parallel with a single core CPC bypassing the ATS going directly to the MDP.

Building Picture

Building photo

Deficiencies (1)

Deficiency #1 RAC 2 Open

Location: ATS door

Category: Improper Use / Damaged

Equipment: ATS

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 642: Inspection

Action Taken: N/A

SOR Issued To: O&M Provider

Description: A crowbar has been wedged against the door to keep it closed as the door locking mechanism is damaged.

Deficiency photo

Signatures & QC

Inspector 1: Giles Edwards

Inspector 2: Jon Sharp

QC: David Forbes (approved 04-JUN-2026)