Inspection-Report_TFSAFE_Full_7NX32_Hangar-RM-5_128_20-06-26_1-3
Pending QCReport Details
- TAG-ID
- TFSAFE_7NX32_Hangar-RM-5_128_20-06-26
- Work Order
- TFS-7NX32-2026-00014
- Site
- H-5 (Jordan) (7NX32)
- Building
- Hangar-RM-5
- Building Type
- HANGAR
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 20-JUN-2026
- Team
- 128
- Overall Rating
- Fair
- Location
- Hangar is located adjacent to the flightline. Rm-5 battery storage is located on right side of building as entered from the car park, West wall.
Building Picture
Deficiencies (3)
Location: LED drivers at light fixtures.
Category: Unlisted Equipment
Equipment: LTG
Occurrences: 2
Imminent Danger: No
Code Source: British Standard
Code Reference: 511: Compliance with standards
Action Taken: N/A
SOR Issued To: O&M Provider
Description: LED drivers are unlisted data sheet required.
Location: Socket ride side wall.
Category: Improper Terminations
Equipment: WLT
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: CPC has been damage at crimp.
Location: LED drivers at Emergency pack light fixtures.
Category: Grounding and Bonding
Equipment: LTG
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Exposed copper at terminals.
Signatures & QC
Inspector 1: Andrew McLean (signed 2026-06-20)
Inspector 2: Brett Smithson (signed 2026-06-20)
Status History
1
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 20-JUN-2026 | Draft | Pending QC | Andrew McLean |