Report Details

TAG-ID
TFSAFE_7NX32_Hangar-RM-5_128_20-06-26
Work Order
TFS-7NX32-2026-00014
Site
H-5 (Jordan) (7NX32)
Building
Hangar-RM-5
Building Type
HANGAR
System Voltage
230/400
Code Standard
British Standard

Inspection Info

Phase
Full Inspection
Date
20-JUN-2026
Team
128
Overall Rating
Fair
Location
Hangar is located adjacent to the flightline. Rm-5 battery storage is located on right side of building as entered from the car park, West wall.

Building Picture

Building photo

Deficiencies (3)

Deficiency #1 RAC 2 Open

Location: LED drivers at light fixtures.

Category: Unlisted Equipment

Equipment: LTG

Occurrences: 2

Imminent Danger: No

Code Source: British Standard

Code Reference: 511: Compliance with standards

Action Taken: N/A

SOR Issued To: O&M Provider

Description: LED drivers are unlisted data sheet required.

Deficiency photo
Deficiency #2 RAC 2 Closed / Repaired

Location: Socket ride side wall.

Category: Improper Terminations

Equipment: WLT

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 526: Electrical connections

Action Taken: N/A

SOR Issued To: O&M Provider

Description: CPC has been damage at crimp.

Deficiency photo
Deficiency #3 RAC 2 Closed / Repaired

Location: LED drivers at Emergency pack light fixtures.

Category: Grounding and Bonding

Equipment: LTG

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 526: Electrical connections

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Exposed copper at terminals.

Deficiency photo

Signatures & QC

Inspector 1: Andrew McLean (signed 2026-06-20)

Inspector 2: Brett Smithson (signed 2026-06-20)

Status History

1
DateFromToChanged ByNotes
20-JUN-2026DraftPending QCAndrew McLean
Back to Work OrderAll Reports