Inspection-Report_TFSAFE_Full_ALQ26_GEN-2-W_113_20-06-26_0
Pending QCReport Details
- TAG-ID
- TFSAFE_ALQ26_GEN-2-W_113_20-06-26
- Work Order
- TFS-ALQ26-2026-00017
- Site
- Al Quwayrah (ALQ26)
- Building
- GEN-2-W
- Building Type
- GENERATOR
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 20-JUN-2026
- Team
- 113
- Overall Rating
- Fair
- Location
- Located on the western perimeter.
Summary of Findings
GEN-2 of 3. Generator serial number - LWL10993. Generator is on standby, not running at this time. All cabling, terminations, and earthing arrangements. Neutral/earth link is located at the MDP. No LHS deficiencies found. GEN-2 ground electrode conductor is 300mm2 and is run from the MET within GEN-1 and via the MET within the ATS, then terminating to two ground rods spaced 9ft apart.
Building Picture
Deficiencies (0)
No deficiencies recorded yet.
Signatures & QC
Inspector 1: Jon Sharp (signed 2026-06-20)
Inspector 2: Giles Vincent-Edwards (signed 2026-06-20)
Status History
1
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 20-JUN-2026 | Draft | Pending QC | Jonathan Sharp |