Inspection-Report_TFSAFE_Full_7NX32_Hangar-RM-5-CDP_128_20-06-26_1-2
Pending QCReport Details
- TAG-ID
- TFSAFE_7NX32_Hangar-RM-5-CDP_128_20-06-26
- Work Order
- TFS-7NX32-2026-00015
- Site
- H-5 (Jordan) (7NX32)
- Building
- Hangar-RM-5-CDP
- Building Type
- HANGAR
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 20-JUN-2026
- Team
- 128
- Overall Rating
- Fair
- Location
- Hangar is located adjacent to the flightline. Rm-5 battery storage is located on right side of building as entered from the car park, west wall.
Summary of Findings
No LHS found at time of inspection, Room 5 CDP inspected.
Building Picture
Deficiencies (2)
Location: RCD in CDP.
Category: Improper Terminations
Equipment: CDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Supply Live and Neutral has not been connected correctly as per manufactures instructions.
Location: RCD in CDP.
Category: Improper Use / Damaged
Equipment: CDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 132: Protection against electric shock
Action Taken: N/A
SOR Issued To: O&M Provider
Description: There is a type AC RCD installed at CDP.