Report Details

TAG-ID
TFSAFE_7NX32_Hangar-RM-3_128_20-06-26
Work Order
TFS-7NX32-2026-00013
Site
H-5 (Jordan) (7NX32)
Building
Hangar-RM-3
Building Type
HANGAR
System Voltage
230/400
Code Standard
British Standard

Inspection Info

Phase
Full Inspection
Date
20-JUN-2026
Team
128
Overall Rating
Fair
Location
Hangar is located adjacent to the flightline. Rm-5 battery storage is located on right side of building as entered from the car park, West wall.

Building Picture

Building photo

Deficiencies (5)

Deficiency #1 RAC 2 Open

Location: LED drivers at light fixtures.

Category: Unlisted Equipment

Equipment: LTG

Occurrences: 20

Imminent Danger: No

Code Source: British Standard

Code Reference: 511: Compliance with standards

Action Taken: N/A

SOR Issued To: O&M Provider

Description: LED drivers are unlisted data sheet required.

Deficiency photo
Deficiency #2 RAC 2 Closed / Repaired

Location: Lighting.

Category: Improper Use / Damaged

Equipment: LTG

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 411: Protection against fire caused by electrical equipment

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Lighting circuit is fed from 16A MCB switch is rated at 10A.

Deficiency photo
Deficiency #3 RAC 2 Open

Location: A/C unit back room right side.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 526: Electrical connections

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Live and neutral has reverse polarity.

Deficiency photo
Deficiency #4 RAC 2 Closed / Repaired

Location: A/C ceiling unit at CDP and first room on the right.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 132: Protection against electric shock

Action Taken: N/A

SOR Issued To: O&M Provider

Description: A/C unit has only 3 core cable no CPC present from outside to internal unit.

Deficiency photo
Deficiency #5 RAC 2 Closed / Repaired

Location: A/C ceiling unit first room on the right.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 642: Inspection

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Green and yellow core has been used as a live conductor.

Deficiency photo

Signatures & QC

Inspector 1: Andrew McLean (signed 2026-06-20)

Inspector 2: Brett Smithson (signed 2026-06-20)