Inspection-Report_TFSAFE_Full_7NX32_Hangar-RM-6-CDP_128_22-06-26_1
QC RejectedReport Details
- TAG-ID
- TFSAFE_7NX32_Hangar-RM-6-CDP_128_22-06-26
- Work Order
- TFS-7NX32-2026-00019
- Site
- H-5 (Jordan) (7NX32)
- Building
- Hangar-RM-6-CDP
- Building Type
- HANGAR
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 22-JUN-2026
- Team
- 128
- Overall Rating
- Fair
- Location
- Hangar is located adjacent to the flightline. Rm-6 is located on right side of building as entered from the car park, west wall.
Summary of Findings
No LHS found at time of inspection, Room 6 CDP inspected.
Building Picture
Update Report
Deficiencies (1)
Location: Top of CDP.
Category: Improper Use / Damaged
Equipment: CDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 522: Selection and erection of wiring systems in relation to external influences
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Holes present at unused cable entry.
Signatures & QC
Comments: Good afternoon gents, please see below for items requiring attention: 1. Summary of findings states - No LHS found at time of inspection – the report has 1 LHS deficiency, this statement should be deleted from the summary. 2. Def 1 – Number of occurrences does not match previous report – change from 1 to 3. If you have any questions, please give me a call.
Please address the issues above and resubmit.
Status History
2
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 23-JUN-2026 | Pending QC | QC Rejected | Hugh Crawford | Good afternoon gents, please see below for items requiring attention: 1. Summary of findings states - No LHS found at time of inspection – the report has 1 LHS deficiency, this statement should be deleted from the summary. 2. Def 1 – Number of occurrences does not match previous report – change from 1 to 3. If you have any questions, please give me a call. |
| 22-JUN-2026 | Draft | Pending QC | Brett Smithson |