Inspection-Report_TFSAFE_Full_7NX32_Hangar-RM-6_128_22-06-26_1-4
QC RejectedReport Details
- TAG-ID
- TFSAFE_7NX32_Hangar-RM-6_128_22-06-26
- Work Order
- TFS-7NX32-2026-00020
- Site
- H-5 (Jordan) (7NX32)
- Building
- Hangar-RM-6
- Building Type
- HANGAR
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 22-JUN-2026
- Team
- 128
- Overall Rating
- Fair
- Location
- Hangar is located adjacent to the flightline. Rm-6 is located on right side of building as entered from the car park, West wall.
Building Picture
No building image uploaded yet.
Update Report
Deficiencies (4)
Location: Above ceiling at light fittings.
Category: Unlisted Equipment
Equipment: LTG
Occurrences: 9
Imminent Danger: No
Code Source: British Standard
Code Reference: 511: Compliance with standards
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Unlisted LED driver.
Location: ack wall at Socket.
Category: Improper Terminations
Equipment: WLT
Occurrences: 2
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: CPC's not crimped sufficiently.
Location: All AC units on back wall.
Category: Grounding and Bonding
Equipment: WLT
Occurrences: 3
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: AC units back wall.
Location: Double pole switch, back wall left side.
Category: Improper Use / Damaged
Equipment: WLT
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 522: Selection and erection of wiring systems in relation to external influences
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Double pole switch and conduit are loose: not secured to wall.
Signatures & QC
Comments: Good afternoon gents, please see below for items requiring attention: 1. No building picture – please add a building picture. 2. Def 2 location – Typos – change ‘ack wall at Socket.’ To ‘ Back wall, at socket. ‘ 3. Def 3 description – change description to - CPC is poorly terminated. 4. If you have any questions, please give me a call
Please address the issues above and resubmit.
Status History
2
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 23-JUN-2026 | Pending QC | QC Rejected | - | Good afternoon gents, please see below for items requiring attention: 1. No building picture – please add a building picture. 2. Def 2 location – Typos – change ‘ack wall at Socket.’ To ‘ Back wall, at socket. ‘ 3. Def 3 description – change description to - CPC is poorly terminated. 4. If you have any questions, please give me a call |
| 22-JUN-2026 | Draft | Pending QC | Andrew McLean |