Report Details

TAG-ID
TFSAFE_ALQ26_MDP-W_113_23-06-26
Work Order
TFS-ALQ26-2026-00019
Site
Al Quwayrah (ALQ26)
Building
MDP-W
Building Type
MDP
System Voltage
230/400
Code Standard
British Standard

Inspection Info

Phase
Full Inspection
Date
23-JUN-2026
Team
113
Overall Rating
Poor
Location
Located on the western perimeter within gen-pad.

Summary of Findings

x 1 MDP comprised of two cabinets. Cabinet 1: x 1 spring loaded main MCCB. Cabinet 2: x 2 600A 3P MCCB's, x 1 400A 3P MCCB. All cabling, terminations, and earthing arrangements. Single core conductors run separately through a ferrous gland plate. The risk of eddy currents generating excessive heat is deemed to be negligible after load test. Neutral/earth link is located within MDP. Ze readings are within the maximum permitted tolerance of 0.35 Ohms.

Building Picture

Building photo

Deficiencies (6)

Deficiency #1 RAC 2 Open

Location: MDP, cabinet 1 and cabinet 2.

Category: Improper Use / Damaged

Equipment: MDP

Occurrences: 2

Imminent Danger: No

Code Source: British Standard

Code Reference: 642: Inspection

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Locking mechanism to door is damaged and secured with wire. Gen-pad is fenced off and locked, restricting access.

Deficiency photo
Deficiency #2 RAC 2 Open

Location: Within MDP, cabinet 1 and cabinet 2.

Category: Improper Use / Damaged

Equipment: MDP

Occurrences: 2

Imminent Danger: No

Code Source: British Standard

Code Reference: 132: Protection against electric shock

Action Taken: N/A

SOR Issued To: O&M Provider

Description: No dead fronts present within MDP. Gen-pad is fenced off and locked, restricting access.

Deficiency photo
Deficiency #3 RAC 3 Open

Location: Within MDP, cabinet 1 and cabinet 2.

Category: Poor Workmanship

Equipment: SDP

Occurrences: 24

Imminent Danger: No

Code Source: British Standard

Code Reference: 510: Common rules

Action Taken: N/A

SOR Issued To: O&M Provider

Description: SWA glands are not fixed into position, removing required abrasion protection.

Deficiency photo
Deficiency #4 RAC 2 Open

Location: MDP, cabinet 1 and cabinet 2.

Category: Grounding and Bonding

Equipment: GND

Occurrences: 24

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: SWA glands are not fixed into position, removing required earthing to steel wire armouring.

Deficiency photo
Deficiency #5 RAC 3 Open

Location: Within MDP, cabinet 2, circuit 1/TP.

Category: Poor Workmanship

Equipment: MDP

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 510: Common rules

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Redundant circuit has not been safely removed, leaving energized bare ends exposed.

Deficiency photo
Deficiency #6 RAC 3 Open

Location: Within MDP, cabinet 2, circuit 2/TP.

Category: Poor Workmanship

Equipment: MDP

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 526: Electrical connections

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Excessive copper conductor exposed to L3.

Deficiency photo