Inspection-Report_TFSAFE_Full_ALQ26_MDP-W_113_23-06-26_1-6
Pending QCReport Details
- TAG-ID
- TFSAFE_ALQ26_MDP-W_113_23-06-26
- Work Order
- TFS-ALQ26-2026-00019
- Site
- Al Quwayrah (ALQ26)
- Building
- MDP-W
- Building Type
- MDP
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 23-JUN-2026
- Team
- 113
- Overall Rating
- Poor
- Location
- Located on the western perimeter within gen-pad.
Summary of Findings
x 1 MDP comprised of two cabinets. Cabinet 1: x 1 spring loaded main MCCB. Cabinet 2: x 2 600A 3P MCCB's, x 1 400A 3P MCCB. All cabling, terminations, and earthing arrangements. Single core conductors run separately through a ferrous gland plate. The risk of eddy currents generating excessive heat is deemed to be negligible after load test. Neutral/earth link is located within MDP. Ze readings are within the maximum permitted tolerance of 0.35 Ohms.
Building Picture
Deficiencies (6)
Location: MDP, cabinet 1 and cabinet 2.
Category: Improper Use / Damaged
Equipment: MDP
Occurrences: 2
Imminent Danger: No
Code Source: British Standard
Code Reference: 642: Inspection
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Locking mechanism to door is damaged and secured with wire. Gen-pad is fenced off and locked, restricting access.
Location: Within MDP, cabinet 1 and cabinet 2.
Category: Improper Use / Damaged
Equipment: MDP
Occurrences: 2
Imminent Danger: No
Code Source: British Standard
Code Reference: 132: Protection against electric shock
Action Taken: N/A
SOR Issued To: O&M Provider
Description: No dead fronts present within MDP. Gen-pad is fenced off and locked, restricting access.
Location: Within MDP, cabinet 1 and cabinet 2.
Category: Poor Workmanship
Equipment: SDP
Occurrences: 24
Imminent Danger: No
Code Source: British Standard
Code Reference: 510: Common rules
Action Taken: N/A
SOR Issued To: O&M Provider
Description: SWA glands are not fixed into position, removing required abrasion protection.
Location: MDP, cabinet 1 and cabinet 2.
Category: Grounding and Bonding
Equipment: GND
Occurrences: 24
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To: O&M Provider
Description: SWA glands are not fixed into position, removing required earthing to steel wire armouring.
Location: Within MDP, cabinet 2, circuit 1/TP.
Category: Poor Workmanship
Equipment: MDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 510: Common rules
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Redundant circuit has not been safely removed, leaving energized bare ends exposed.
Location: Within MDP, cabinet 2, circuit 2/TP.
Category: Poor Workmanship
Equipment: MDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Excessive copper conductor exposed to L3.
Signatures & QC
Inspector 1: Jon Sharp (signed 2026-06-23)
Inspector 2: Giles Vincent-Edwards (signed 2026-06-23)
Status History
1
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 23-JUN-2026 | Draft | Pending QC | Jonathan Sharp |