Inspection-Report_TFSAFE_Full_7NX32_Hangar-CDP_128_23-06-26_1-2
Pending QCReport Details
- TAG-ID
- TFSAFE_7NX32_Hangar-CDP_128_23-06-26
- Work Order
- TFS-7NX32-2026-00022
- Site
- H-5 (Jordan) (7NX32)
- Building
- Hangar-CDP
- Building Type
- HANGAR
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 23-JUN-2026
- Team
- 128
- Overall Rating
- Fair
- Location
- Hangar is located adjacent to the flight line opposite Expansion Area entrance. CDP is located on the LHS within hangar between the latrines.
Summary of Findings
Inspected hangar CDP.
Building Picture
Deficiencies (2)
Deficiency #1 RAC 2 Closed / Repaired
Location: Within CDP.
Category: Improper Use / Damaged
Equipment: CDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 132: Protection against electric shock
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Incorrect RCD within the CDP. Type AC RCD is installed.
Deficiency #2 RAC 2 Open
Location: Within CDP & Lighting Circuit.
Category: Improper Use / Damaged
Equipment: CDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 511: Compliance with standards
Action Taken: N/A
SOR Issued To: O&M Provider
Description: An oversized OCPD B20 MCB is used on electrical equipment rated for 10A.
Signatures & QC
Inspector 1: Brett Smithson (signed 2026-06-23)
Inspector 2: Andrew McLean (signed 2026-06-23)
Status History
1
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 23-JUN-2026 | Draft | Pending QC | Brett Smithson |