Permit Information

EEWIP-20260604-001
04-JUN-2026
Team 113
Al Quwayrah
MDP-N
Inspection
Not authorized to de-energize MDP-N as it feeds critical facilities.

Shock Hazard Analysis

400V
Inspection and testing of ATS
Exposed energized conductors
00
1 ft 0 in.

Flash Hazard Analysis

400V
4.0 cal/cm²
4 ft min
8 cal/cm²
CAT II

Lock Out Tag Out

Energy Sources IdentifiedYes
PPE CAT II DonnedYes
Personnel NotifiedYes
Equipment ShutdownNo
Electrically Safe ConditionYes

PPE Evidence Photo

LOTO Signatures

Giles Edwards
04-JUN-2026
Jon Sharp
04-JUN-2026
electrical
Giles Edwards
Jon Sharp

Completion

Inspection CompletedYes
Reenergization NotifiedNo
Isolating Devices RemovedNo
Equipment ReenergizedYes
Giles Edwards
04-JUN-2026

Review Information

Approved
04-JUN-2026