Report Details

TAG-ID
TFSAFE_KFAB22_Oiltown-Fire-CHU_116_16-06-26_1-8
Work Order
TFS-KFAB22-2026-00016
Site
KFAB (Jordan) (KFAB22)
Building
Oiltown-Fire-CHU
Building Type
ACCOMM
System Voltage
230/400
Code Standard
British Standard

Inspection Info

Phase
Full Inspection
Date
16-JUN-2026
Team
116
Overall Rating
Fair
Location
Oiltown is adjacent to the airfield, north of Dufftown. The Fire CHU is within Oiltown.

Summary of Findings

Items inspected: 1 x CDP. 3 x Internal lights. 3 x External lights 3 x Double sockets. 3x Single sockets. 3 x 2-gang switches. 6 x AC isolators for 3 x AC systems.

Building Picture

Building photo

Deficiencies (8)

Deficiency #1 RAC 2 Open

Location: At CDP.

Category: Improper Use / Damaged

Equipment: CDP

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 132: Protection against electric shock

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Breaker blank missing from dead front.

Deficiency photo
Deficiency #2 RAC 2 Open

Location: Within the CDP.

Category: Improper Use / Damaged

Equipment: CDP

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 132: Protection against electric shock

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Type AC RCD used. Type AC RCD is not suitable for this building.

Deficiency photo
Deficiency #3 RAC 2 Open

Location: Within the CDP.

Category: Improper Terminations

Equipment: CDP

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 526: Electrical connections

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Twist taped connection made to main neutral.

Deficiency photo
Deficiency #4 RAC 2 Open

Location: Within lighting circuit including switches.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 1

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: No CPC to lighting circuit.

Deficiency photo
Deficiency #5 RAC 2 Open

Location: Internal light fittings.

Category: Improper Terminations

Equipment: WLT

Occurrences: 6

Imminent Danger: No

Code Source: British Standard

Code Reference: 526: Electrical connections

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Twist taped connections made to live and neutral.

Deficiency photo
Deficiency #6 RAC 2 Open

Location: All circuits.

Category: Grounding and Bonding

Equipment: WLT

Occurrences: 6

Imminent Danger: No

Code Source: British Standard

Code Reference: 542: Earthing arrangements

Action Taken: N/A

SOR Issued To: O&M Provider

Description: High Zs reading of 2.44 ohms throughout the CHU.

Deficiency photo
Deficiency #7 RAC 2 Open

Location: At external AC condensers.

Category: Unlisted Equipment

Equipment: WLT

Occurrences: 3

Imminent Danger: No

Code Source: British Standard

Code Reference: 511: Compliance with standards

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Unlisted cables.

Deficiency photo
Deficiency #8 RAC 2 Open

Location: At external AC condensers.

Category: Improper Use / Damaged

Equipment: WLT

Occurrences: 3

Imminent Danger: No

Code Source: British Standard

Code Reference: 522: Selection and erection of wiring systems in relation to external influences

Action Taken: N/A

SOR Issued To: O&M Provider

Description: Cable clips not used: strain on terminations.

Deficiency photo

Signatures & QC

Inspector 1: Salomon Munoz

Inspector 2: Jongi Ledbetter

QC: Hugh Crawford (approved 18-JUN-2026)

Status History

4
DateFromToChanged ByNotes
18-JUN-2026Pending QCQC ApprovedHugh Crawford
17-JUN-2026QC RejectedPending QCSalomon Munoz
17-JUN-2026Pending QCQC Rejected-Hi gents, please see items below which require attention: - First line of summary has a typo - change 'tems inspected:' to Items inspected: - Def 6 - Photo is upside down - Def 7 - No equipment category entered for the deficiency
16-JUN-2026DraftPending QCSalomon Munoz
📄 Download PDFCreate Re-inspection 1Back to Work OrderAll Reports