Inspection-Report_TFSAFE_Full_KFAB22_Oiltown-Fire-CHU_116_16-06-26_1-8
CompleteReport Details
- TAG-ID
- TFSAFE_KFAB22_Oiltown-Fire-CHU_116_16-06-26_1-8
- Work Order
- TFS-KFAB22-2026-00016
- Site
- KFAB (Jordan) (KFAB22)
- Building
- Oiltown-Fire-CHU
- Building Type
- ACCOMM
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 16-JUN-2026
- Team
- 116
- Overall Rating
- Fair
- Location
- Oiltown is adjacent to the airfield, north of Dufftown. The Fire CHU is within Oiltown.
Summary of Findings
Items inspected: 1 x CDP. 3 x Internal lights. 3 x External lights 3 x Double sockets. 3x Single sockets. 3 x 2-gang switches. 6 x AC isolators for 3 x AC systems.
Building Picture
Deficiencies (8)
Location: At CDP.
Category: Improper Use / Damaged
Equipment: CDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 132: Protection against electric shock
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Breaker blank missing from dead front.
Location: Within the CDP.
Category: Improper Use / Damaged
Equipment: CDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 132: Protection against electric shock
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Type AC RCD used. Type AC RCD is not suitable for this building.
Location: Within the CDP.
Category: Improper Terminations
Equipment: CDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Twist taped connection made to main neutral.
Location: Within lighting circuit including switches.
Category: Grounding and Bonding
Equipment: WLT
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To: O&M Provider
Description: No CPC to lighting circuit.
Location: Internal light fittings.
Category: Improper Terminations
Equipment: WLT
Occurrences: 6
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Twist taped connections made to live and neutral.
Location: All circuits.
Category: Grounding and Bonding
Equipment: WLT
Occurrences: 6
Imminent Danger: No
Code Source: British Standard
Code Reference: 542: Earthing arrangements
Action Taken: N/A
SOR Issued To: O&M Provider
Description: High Zs reading of 2.44 ohms throughout the CHU.
Location: At external AC condensers.
Category: Unlisted Equipment
Equipment: WLT
Occurrences: 3
Imminent Danger: No
Code Source: British Standard
Code Reference: 511: Compliance with standards
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Unlisted cables.
Location: At external AC condensers.
Category: Improper Use / Damaged
Equipment: WLT
Occurrences: 3
Imminent Danger: No
Code Source: British Standard
Code Reference: 522: Selection and erection of wiring systems in relation to external influences
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Cable clips not used: strain on terminations.
Signatures & QC
Inspector 1: Salomon Munoz
Inspector 2: Jongi Ledbetter
QC: Hugh Crawford (approved 18-JUN-2026)
Status History
4
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 18-JUN-2026 | Pending QC | QC Approved | Hugh Crawford | |
| 17-JUN-2026 | QC Rejected | Pending QC | Salomon Munoz | |
| 17-JUN-2026 | Pending QC | QC Rejected | - | Hi gents, please see items below which require attention: - First line of summary has a typo - change 'tems inspected:' to Items inspected: - Def 6 - Photo is upside down - Def 7 - No equipment category entered for the deficiency |
| 16-JUN-2026 | Draft | Pending QC | Salomon Munoz |