Inspection-Report_TFSAFE_Full_7NX32_Hangar-RM-4-CDP_128_19-06-26_1-4
QC RejectedReport Details
- TAG-ID
- TFSAFE_7NX32_Hangar-RM-4-CDP_128_19-06-26
- Work Order
- TFS-7NX32-2026-00011
- Site
- H-5 (Jordan) (7NX32)
- Building
- Hangar-RM-4-CDP
- Building Type
- CDP
- System Voltage
- 230/400
- Code Standard
- British Standard
Inspection Info
- Phase
- Full Inspection
- Date
- 19-JUN-2026
- Team
- 128
- Overall Rating
- Fair
- Location
- Hangar is located adjacent to the flightline.
Summary of Findings
No LHS found at time of inspection, Room 4 CDP inspected.
Building Picture
Update Report
Deficiencies (4)
Location: RCD within the CDP.
Category: Improper Use / Damaged
Equipment: CDP
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Live and neutral have not been terminated in the correct terminals of the RCD as per manufacturer's instructions.
Location: RCD within the CDP.
Category: Improper Terminations
Equipment: WLT
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Main earthing conductor within the CDP has been cut to fit the terminal.
Location: Within the CDP.
Category: Improper Terminations
Equipment: WLT
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 526: Electrical connections
Action Taken: N/A
SOR Issued To: O&M Provider
Description: Poor termination with exposed copper within the CDP.
Location: RCD within the CDP.
Category: Improper Use / Damaged
Equipment: WLT
Occurrences: 1
Imminent Danger: No
Code Source: British Standard
Code Reference: 132: Protection against electric shock
Action Taken: N/A
SOR Issued To: O&M Provider
Description: There is a type AC RCD installed within the CDP.
Signatures & QC
Comments: Good afternoon gents, Please see below for items requiring attention: 1. Building location - please provide more information; where is room 4 within the hangar 2. Summary of findings – Summary says No LHS issues were found; the report has 2 deficiencies – this statement can be deleted 3. Def 1, 3, and 4 were closed on re-inspection-1 13-Jan-26; unless these issues are still present, they should be removed from this report 4. Def 2 – location is incorrect – Def does not relate to the RCD - change RCD within the CDP. to Within the CDP. If you have any questions, please give me a call
Please address the issues above and resubmit.
Status History
2
| Date | From | To | Changed By | Notes |
|---|---|---|---|---|
| 20-JUN-2026 | Pending QC | QC Rejected | Hugh Crawford | Good afternoon gents, Please see below for items requiring attention: 1. Building location - please provide more information; where is room 4 within the hangar 2. Summary of findings – Summary says No LHS issues were found; the report has 2 deficiencies – this statement can be deleted 3. Def 1, 3, and 4 were closed on re-inspection-1 13-Jan-26; unless these issues are still present, they should be removed from this report 4. Def 2 – location is incorrect – Def does not relate to the RCD - change RCD within the CDP. to Within the CDP. If you have any questions, please give me a call |
| 19-JUN-2026 | Draft | Pending QC | Andrew McLean |